Trane Performance Air Handlers Manuel d'installation Page 51

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 100
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 50
CAH-SVX01B-EN 51
Installation - Mechanical
Bag or Cartridge Filters
1. Disconnect power to the unit.
2. Keeping the bag filters folded, slide each filter into the filter rack, pushing them tightly against
the unit. Pleats should be in the vertical position.
3. If using optional pre-filters, slide them into the appropriate filter rack.
4. If block-offs are provided with the unit, slide the block-offs into the filter track.
5. Close and secure the access door, making certain the door closes snug against the rack.
Note: The block-off is intended to make a seal when the access door is closed. It may require a few
adjustments to ensure a proper seal.
Figure 48. Filter block-off placement
Vue de la page 50
1 2 ... 46 47 48 49 50 51 52 53 54 55 56 ... 99 100

Commentaires sur ces manuels

Pas de commentaire