Start-Up
28 GHND-SVX01C-EN
b. The indirect spark ignition system consists of an
ignition control module, a dual combination gas
valve, and a spark-ignited pilot burner. When the
pressure switch closes, the pilot valve opens and a
spark is generated to light the pilot burner. When
the flame sensing circuit senses that pilot flame is
established, the main gas valve is opened to supply
gas to the main burners. When the thermostat is
satisfied, the vent system is de-energized and both
valves are closed to stop all flow of gas to the unit.
2. The limit switch interrupts the flow of electric current to
the main gas valve in case the heater becomes
overheated.
3. The fan switch delays the operation of the fan
until the
heater is warmed, then keeps the fan running after the
gas has been turned off until the useful heat has been
removed. The start-up fan delay must not exceed
90 seconds from a cold start.
4. The wall thermostat (supplied optionally) is a
tempera
ture sensitive switch which operates the vent
system and ignition system to control the temperature
of the space being heated. It must be mounted on a
vibration free, vertical surface away from air currents,
in accordance with the instructions furnished with the
thermostat (also refer to “Installation: Electrical,
p. 24).
Start-Up
Note: Also refer to the lighting instruction plate equipped
on the unit.
1. Open the manual valve supplying gas to the unit
heater, and with the union connection loose, purge air
from the gas line. Tighten the union and check for gas
leaks, using a soapy water solution only.
2. Open the manual valve on the unit heater.
3. Turn ON electrical power.
4. The unit should be under the control of the thermostat.
T
urn the thermostat to the highest point and determine
that the power venter motor starts and the pilot and
main burners ignite. Turn the thermostat to the lowest
point and determine that the power venter motor shuts
off and pilot and main burners are extinguished.
5. If pilot adjustment is required, remove the pilot
a
djustment seal cap and adjust the pilot screw to
obtain proper flame. Clockwise rotation decreases
pilot flame size. Replace the cap.
6. Turn the thermostat to
the desired position.
7. Refer to “Gas Input Rate,” p. 30 and “Gas Pressure
Adjustments,” p. 30 for more specifications.
Shut-Down
1. Turn the valve selector knob to the OFF” position.
2. Turn off the electricity.
3. To relight, follow the instructions in “Start-Up,” p. 28
(preceding section).
See Figure 21, p. 29 for parts/identification.
NOTICE:
Additional Devices!
The addition of external draft hoods or power venters is
not permitted. Addition of such devices could cause
severe unit malfunction or failure!
WARNING
Hazard of Explosion!
Never use an open flame to detect gas leaks. Explosive
conditions may occur. Use a leak test solution or other
approved methods for leak testing. Before attempting
to light or relight the pilot, wait 5 minutes to allow gas
which may have accumulated in the burner
compartment to escape. Failure to follow
recommended safe leak test procedures or pilot
lighting/relighting instructions could result in death or
serious injury or equipment or property-only-damage.