Trane Modular 20 to 35 Tons Liste des pièces Page 43

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 88
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 42
PKG-PRC003U-EN 43
Controls
Refrigeration fail relay
Heat fail relay
Supply fan fail relay
Active diagnostics
Analog inputs
Occupied zone cooling setpoint
Occupied zone heating setpoint
Unoccupied zone cooling setpoint
Unoccupied zone heating setpoint or minimum outside air flow setpoint
Supply air cooling setpoint
Supply air heating setpoint
Supply air static pressure setpoint Comparative Enthalpy Option (ECEM)
Analog inputs
Return air temperature
Return air humidity Ventilation Override Module Option (VOM)
Binary inputs
VOM mode A, unit off
VOM mode B, pressurize
VOM mode C, exhaust
VOM mode D, purge
VOM mode E, purge w/duct pressure control
Binary output
V.O. relay
LonTalk™ Building Automation System
The LonTalk Communication Interface for IntelliPak self-contained (LCI-I) controller expands
communications from the unit UCM network to aTrane Tracer Summit or a 3rd party building
automation system, utilizing LonTalk, and allows external setpoint and configuration adjustment
and monitoring of status and diagnostics.The LCI-I utilizes an FTT-10A FreeTopology transceiver,
which supports nonpolarity sensitive, free topology wiring, which allows the system installer to
utilize star, bus, and loop architectures.This controller works in standalone mode, peer-to-peer with
one or more other units, or when connected to aTrane Tracer Summit or a 3rd party building
automation system that supports LonTalk.
BACnet™ Building Automation System
The BACnet Communication Interface for IntelliPak self-contained (BCI-I) controller expands
communications from the unit UCM network toTracer SC or a 3rd party building automation
system, utilizing BACnet, and allows external setpoint and configuration adjustment and
monitoring of status and diagnostics.The BCI-I utilizes the BACnet defined MS/TP protocol as
defined in ASHRAE standard135-2004.This controller works in standalone mode, with Tracer SC
or when connected to a 3rdparty building automation system that supports BACnet
Vue de la page 42
1 2 ... 38 39 40 41 42 43 44 45 46 47 48 ... 87 88

Commentaires sur ces manuels

Pas de commentaire