PKG-PRC003U-EN 47
Controls
VO relay – energized
Exhaust fan (field-installed) - on
Exhaust damper (field-installed) - open
Purge with duct pressure control “E”.
This sequence can be used when supply air control is required for smoke control.
Supply fan – on
Supply fan VFD – on (if equipped)
Outside air dampers – open
Heat – all stages – off, modulating heat output at 0 vdc
Occupied/unoccupied output – energized
VO relay – energized
Exhaust fan (field-installed) - on
Exhaust damper (field-installed) - open
Note: Each system (cooling, exhaust, supply air, etc.) within the unit can be redefined in the field
for each of the five sequences, if required. Also the definitions of any or all of the five
sequences may be locked into the software by simple key strokes at the human interface
panel.
Generic Building Automation System Module (GBAS)
The generic building automation system module (GBAS) provides broad control capabilities for
building automation systems other thanTrane’sTracer system. A field provided potentiometer or
a 0-5 vdc signal can be applied to any of the inputs of the GBAS to provide the following inputs and
outputs.Four analog inputs that can be configured to be any of the following:
1. Occupied zone cooling
2. Unoccupied zone cooling
3. Occupied zone heating
4. Unoccupied zone heating
5. SA cooling setpoint
6. SA heating setpoint
7. Space static pressure setpoint
8. SA static pressure setpoint
Each of the five (5) relay outputs can be mapped to any/all of the available diagnostics.
Demand Limiting Binary Input
This function is operational on units with a GBAS and reduces electrical consumption at peak load
times.There are two types of demand limiting, 50% and 100%. When demand limiting is needed,
mechanical cooling and heating operation are either partially (50%), or completely disabled (100%)
to save energy.The demand limit definition is user definable at the human interface panel. Demand
limit binary input accepts a field supplied switch or contact closure. When the need for demand
limiting has been discontinued, the unit’s cooling/heating functions will again become fully
enabled.
Evaporator Coil Frost Protection FROSTAT™
The FROSTAT system uses a temperature sensor on the evaporator to determine if the coil is
getting close to a freezing condition. If so, mechanical cooling capacity is shed as necessary to
prevent icing.