86 PKG-PRC003U-EN
Mechanical Specifications
the inter-processor communications bridge (IPCB) mounted in the unit with twisted wire pair
communication wiring and 24V wiring.
Generic Building Automation System Module (GBAS)
The GBAS module is for use with a non-Trane building management system.The module provides
a binary input for demand limiting, four analog inputs for setpoint adjustment, and five relay
outputs for diagnostic reporting. Inputs can use a potentiometer or 0-5 vdc signal.
Ventilation Override Module (VOM)
The VOM allows you to program the unit with up to five ventilation sequences: smoke purge,
evacuation, pressurization, purge, and purge with duct control.Typically, a hard-wire short from
a smoke detector or fire control panel will cause a binary input on the VOM to close, thus causing
the programmed sequence to occur.
Tracer LCI-I Communication Interface
The LCI-I provides interface to aTrane Integrated Comfort™ system (ICS) or third party building
management network supporting Lon-Talk communication. It allows remote control and
monitoring of the self-contained unit using a personal computer withTracer building management
software.
BACnet® Building Automation System
The BACnet Communication Interface for IntelliPak self-contained (BCI-I) controller expands
communications from the unit UCM network toTracer SC or a 3rd party building automation
system, utilizing BACnet, and allows external setpoint and configuration adjustment and
monitoring of status and diagnostics.
Wireless Comm Interface - Field Installed
Trane Wireless Comm interface – Provides wireless communication between theTracer™ SC,
Tracer Unit Controllers and BACnet Communication Interface (BCI) modules.
Remote Air-Cooled Condenser CCRC/CIRC
Cabinet
The unit framework shall be formed structural steel members of galvanized steel. Panels and
access doors shall be galvanized steel.The unit exterior shall be phosphatized and finished with
air-dried enamel paint.
Refrigerant Circuits and Controls
All sizes shall have dual refrigerant circuits and include an integral subcooling circuit for each
circuit. All necessary controls to run unit fans shall be factory installed.The control panel shall
include fan motor contactors, terminal block connection for compressor interlock, and 115-volt
control power transformer.
Condenser Coils
The condenser coil arrangement shall be slab type. Coils shall be seamless 3/8-inch OD copper
tubes expanded into aluminum fins. Each circuit shall include an integral subcooler.The coil shall
be leak tested at 650 psig air pressure.
Condenser Fans and Motor
Vertical discharge direct drive fans shall be statically and dynamically balanced at the factory.
Motors shall be three-phase with permanently lubricated ball bearings, built-in current and thermal
overload protection, and weather tight rain slinger over the fan’s shaft.