46 PKG-PRC003U-EN
Controls
UNIT OFF sequence “A”.
When complete system shut down is required, the following sequence can be used:
• Supply fan – off
• Supply fan VFD – off (0 Hz) (if equipped)
• Outside air dampers – closed
• Heat – all stages – off, modulating heat output at 0 vdc
• Occupied/unoccupied output – deenergized
• VO relay – energized
• Exhaust fan (field-installed) - off
• Exhaust damper (field-installed) - closed
PRESSURIZE sequence “B”.
This override sequence can be used if a positively pressured space is desired instead of a negatively
pressurized space.
• Supply fan – on
• Supply fan VFD – on (60 Hz)/VAV boxes – open (if equipped)
• Outside air dampers – open
• Heat – all stages – off, modulating heat output at 0 vdc
• Occupied/unoccupied output - energized
• VO relay - Energized
• Exhaust fan (field-installed) - off
• Exhaust damper (field-installed) - closed
EXHAUST sequence “C”.
With the building’s exhaust fans running and the unit’s supply fan off, the conditioned space
becomes negatively pressurized.This is desirable for clearing the area of smoke when necessary,
i.e. from an extinguished fire, to keep smoke out of areas that were not damaged.
• Supply fan – off
• Supply fan VFD – off (0 Hz) (if equipped)
• Outside air dampers – closed
• Heat – all stages – off, modulating heat output at 0 vdc
• Occupied/unoccupied output – deenergized
• VO relay – energized
• Exhaust fan (field-installed) - on
• Exhaust damper (field-installed) - open
Purge sequence “D”.
This sequence could be used for purging the air out of a building before coming out of Unoccupied
mode of operation on VAV units. Also, it can be used to purge smoke or stale air.
• Supply fan – on
• Supply fan VFD – on (60 Hz)/VAV boxes – open (if equipped)
• Outside air damper – open
• Heat – all stages – off, modulating heat output at 0 vdc
• Occupied/unoccupied output – energized
Commentaires sur ces manuels