Vue de la page 111
11 2 VAV-PRC011M-EN
DDC Controls
Differential Pressure Transducer
Specifications
Input Pressure Range
0.0 to 5.0 in. wg
(Maximum input pressure 5 psig)
Operating Environment
32 to 140° F, (0 to 60°C)
5% to 95% RH, Non-Condensing
Storage Environment
-40 to 180° F, (-40 to 82.2°C)
5% to 95%RH, Non-condensing
Electrical Connections
V
in
= 5.0 VDC nominal
(4.75 to 5.25 VDC acceptable)
Current Draw = 5 mA maximum
Null Voltage = 0.250 VDC ± 0.06 VDC
Span = 3.75 VDC ± 0.08 VDC
Note: Null and Span are ratio-metric with V
in
Physical Dimensions
Width: 2.5" (63.5 mm)
Length: 3.0" (76.2 mm)
Height: 1.5" (38.1 mm)
Pressure Connections
1/8" (3.175 mm) barbed tubing connections
The differential pressure transducer is used in conjunction with the Trane
direct digital controller and analog electronic controller. The pressure
transducer measures the difference between the high-pressure and low-
pressure ports of the Trane flow ring. The transducer is self-adjusting to
changes in environmental temperature and humidity.