VAV-PRC011M-EN 97
DDC Controls
Direct Digital Controller—Unit Control Module (UCM4)
The controller also accepts an auxiliary duct temperature sensor input or a supply air temperature
value from Tracer™ SC. Staged electric heat, pulse width modulated electric heat, proportional hot
water heat or on/off hot water heat control are provided when required. The control board operates
using 24-VAC power. The Trane DDC-UCM is a member of the Trane Integrated Comfort™ systems
(ICS) family of products. When used with a Trane Tracer SC building management controller or
other Trane controllers, zone grouping and unit diagnostic information can be obtained. Also part
of ICS is the factory-commissioning of parameters specified by the engineer (see “Factory-installed
vs. Factory-commissioned,” p. 10 for more details).
Specifications
Supply Voltage
24 VAC, 50/60 Hz
Maximum VA Load
No Heat or Fan
12 VA (Board, Transducer, Zone Sensor, and Actuator)
Note: If using field-installed heat, 24 VAC transformer should be sized for additional load.
Output Ratings
Actuator Output: 24 VAC at 12 VA
1st Stage Reheat: 24 VAC at 12 VA
2nd Stage Reheat: 24 VAC at 12 VA
3rd Stage Reheat: 24 VAC at 12 VA
Binary Input
24 VAC
Auxiliary Input
Can be configured for an optional 2–10 VDC CO
2
sensor, or auxiliary temperature sensor.
Operating Environment:
32 to 140°F, (0 to 60°C)
5% to 95% RH, Non-condensing
Storage Environment
-40 to 180°F (-40 to 82.2°C),
5% to 95%RH, Non-Condensing
Physical Dimensions
Width: 5.5" (139.7 mm)
Length: 2.8" (69.85 mm)
Height: 1.8" (44.45 mm)
The Trane direct digital controller Unit Control
Module (DDC-UCM) is a microprocessor-based
terminal unit with non-volatile memory which
provides accurate airflow and room temperature
control of Trane VAV air terminal units. The UCM can
operate in a pressure-independent or a pressure-
dependent mode and uses a proportional plus
integral control algorithm. The controller monitors
zone temperature setpoints, zone temperature and its
rate of change and valve airflow (via flow ring
differential pressure).